Firepro Insulated Fire Sleeves are a unique combination of Rockwool and Graphite intumescent that provide all the benefits of Rockwool’s thermal, noise and fire benefits with an added intumescent effect.
 |
|
|
 |
| Fire stopping of insulated pipe penetrations |
|
|
Description
For insulated pipes it is normally necessary to remove the insulation at point of penetration to enable standard pipe collars to close plastic pipes. This removal of insulation results in condensation on cold pipes and loss of thermal performance on hot pipes.
Firepro insulated Fire Sleeves avoids this problem by providing both fire stopping and thermal insulation.
Firepro Insulated Fire Sleeves are intended for use on Copper, Mild Steel, Polypropylene and PVC pipes and can provide 1 /2, 1 and 2 hour fire resistance.
Test Data
| Pipe Description - Dia |
2 Hour
Batt |
2 Hour
Brickwork |
2 Hour
Plasterboard |
2 Hour
Solid Floor |
| Steel 22-165mm |
|
X |
X |
X |
| Copper 12-160mm |
|
X |
X |
X |
| Polypropylene 12-28mm |
X |
X |
X |
X |
| PPVC 55-160mm |
X |
X |
|
|
Acoustics
The use of Firepro Insulated Pipe Sleeves can considerably reduce the noise emission from noisy pipework. For higher standards of acoustic insulation please refer to our technical department.
Service Temperatures
Firepro Insulated Fire Sleeves are used to fire stop pipe work operating at temperatures between 0ºC and 180ºC. At low temperatures, care should be taken to maintain the vapour barrier.
Compatibility
Firepro Rockwool is compatible with most materials with which it is likely to come into contact in normal building and industrial applications.
Precautions should be taken when insulating austenitic stainless steel, regardless of insulation type.
Biological
Firepro Rockwool insulation offers no sustenance to vermin and does not encourage the growth of fungi, moulds or bacteria.